Should you fully insulate
under concrete slabs on or below grade?
Below grade comparison
Downward heat loss
tools

Figure 1. Ref.: Foundation heat loss from heated concrete slab-on-grade floors by Pirawas Chuangchid, Ph.D., Moncef Krarti, Ph.D., P.E, Joint Center for Energy Management (JCEM), CEAE Department, University of Colorado at Boulder, Boulder, CO 80309-0428, (CB 428) USA
When evaluating under slab insulation do not
assume:
-
uniform undisturbed ground temperatures
-
no groundwater flow
-
no moisture transport in the upper
-unsaturated regions of the ground
-
uniform heat transfer under the slab,
perimeter foundation and foundation corners
A word on “who” specifies insulation.
Take your everyday building and ask who specifies
the insulation?
When it comes to roofs and walls – it is a given
that it will be based on the building code established with the
participation of building scientist and practicing engineers and
architects who as part of their academic training and
professional development study material and thermal sciences.
However as it happens in the absence of an
enforced energy code, when it comes to insulation under a heated
slab this is often left up to the builders and or mechanical
contractors.
What is the difference?
Well these latter service providers get judged on
meeting
the building code which is based on minimum
requirements.
If there is a decision to improve the building
beyond code and this decision is left up to someone who has not
been trained in material and thermal sciences, it can and does
happen where the substituted materials and methods of
construction are of no benefit even though the client may be
thinking they have received an upgrade because they paid more
for the changes.
This occurs unfortunately when for example
reflective bubble foil insulation is placed under slabs.
Our message – the slab is part of the building
enclosure as such it is under the domain of the building
scientist, architect and engineer and only these professionals
should be making recommendations to the builder, trades and
clients as to how much and what type.
The standard for acceptance for under slab
insulation is Type 2, 3 or 4 EPS or XPS as per the table below.

Figure 4.
All under slab insulation shall have been evaluated to CAN/ULC-S701-03 by the National Research Council's Institute for Research in
Construction (IRC) through the Canadian Construction Materials Centre (CCMC) and must bear the manufacturer's name or trademark and CCMC evaluation listing number. Standard
of Acceptance: Type 2, 3 or 4 as per CAN/ULC-S701-03, Material Properties.
"...all concrete slabs must be provided with
minimum RSI 2.1 (R12) insulation underneath the slab."
Article 9.25.2.1., City of Vancouver, B.C., Canada

Figure 5.
Kehrer, M., Pallin, S.
Hygrothermal Material Properties for Soils in Building Science,
Journal of the National Institute of Building Sciences. October,
2013.
Soils Matter

Figure 6.
Soil Characteristics. Source US Department of
Agriculture
The conductivity of soil is largely affected by
its moister content. Moisture content is largely affected by its
characteristics. Clay based soils will retail moisture more so
than sandy silty soils. One would think anyone offering advice
on under slab insulation should know this stuff but it's not a
requirement nor is it taught to HVAC contractors designing and
installing radiant based HVAC systems.

Figure 7.
Soil conductivities based on type and moisture
content.
|
Should you fully insulate
under concrete slabs on or below grade?
Copyright (c) 2010, Robert Bean, R.E.T., P.L.(Eng.) and
www.healthyheating.com
For additional
support visit our
visitor services page. |
What does physics say? Key
considerations influencing downward heat loss:
-
Soil
characteristics including soil type, moisture
content and density below and adjacent to slabs,
moisture storage function, porosity, conductivity
and specific heat capacity.
-
Water table
characteristics - historical data i.e. risk
assessment for change.
-
Temperatures above
grade and below
grade*
-
Temperature
desired for space conditions
-
Temperatures in
pipe
-
Slab characteristics including
thickness, conductivity and elevation in relation to
grade.
-
Enclosure
performance above and adjacent to the heated slab,
including effects from solar gains. The greater the
performance above the slab, the more significant the
slab heat loss.
-
Tube spacing, slab
conductivities (upward and downward)
-
Tube patterns i.e.
warmest fluid vs. coolest fluid in relation to edge.
-
Aspect ratio of
building that being either the width to length ratio
or area to perimeter ratio i.e. rectangular
buildings vs. square buildings.
*Mean ground temperatures typically run
between 2 and 6 K above mean annual air temperatures. |
Finite element analysis
of uninsulated and insulated heated slabs |
 |
Figure 2. Simulation of a heated slab below grade
with and without insulation. Temperature scale indicated
in degrees Celsius (°C).
Horizontal line with white markers is a reference plane
at approximately 2.4m below the heated slab.
Illustration is representative of a specific condition
at steady state ergo it does not represent every project
and system. |
 |
Figure 3. Simulation of a heated slab on grade with
and without insulation. Temperature scale indicated in
degrees Celsius (°C).
Horizontal line with white markers is a reference plane
at approximately 2.4m below the heated slab.
Illustration is representative of a specific condition
at steady state ergo it does not represent every project
and system. |
What do the building codes
say....
First we should note there are many codes. There are codes
which are enforced federally or regionally. Often the
regional codes are based on federal codes as is the case in
Canada but there is freedom to change or modify
codes to suit regional conditions that may not be addressed
adequately or otherwise in Federal codes. Earthquake
requirements
or naturally ventilated spaces for mild climate zones are two examples where regional
differences may prevail over Federal codes. Secondly, we should
note that building codes are not energy codes unless the
building code includes provisions to address energy over and
above that based on minimum requirements, i.e. the status
quo.
What do we mean by this?
In North America there are
energy standards which exist on a voluntary basis outside
the building code - for example; there is no mandatory
requirement to build homes to the Passivhaus or R2000
standards or to construct buildings and systems to or better
than ASHRAE’s 189.1(2) or ASHRAE 90.1(2). Buildings
constructed to meet or beat these standards would be better
than code. They would be called (wait for it), “better than
code buildings”, or in some cases -
high performance
buildings, but this is confusing since even these are
undefined.
When you build to code you essentially get a “D” grade –
that is, you didn’t fail but you missed the opportunity to
earn an A or A+. If you don’t understand the words, ‘missed
opportunity” then you have never considered what it takes to
increase the insulation under a concrete slab after it has
been poured.
Alright let’s get into it - when it comes to under slab
insulation don’t expect a North American team effort – ya
know the old college, “all for one - one for all” stuff.
Consider this; the March 2010 version of the International
Green Construction Code (IGCC), Table 606.1.1 Prescriptive
Building Thermal Envelope Requirements calls for climate
based perimeter
heat loss factors (F-factor) for slab-on-grade floors
between 0.730 Btu/hr·ft·°F
to 0.373 Btu/hr·ft·°F;
or the Washington State Legislature, WAC 51-11-1002, Section
1002: calling for anywhere between 0.42 Btu/hr·ft·°F
to 0.69 Btu/hr·ft·°F
for various slab depth and wall construction . Residential
Requirements of the 2009 International Energy Conservation
Code provides in Table 402.1.3 Equivalent U-values ( in
units of Btu/hr·ft2·°F)
for floors of 0.028 to 0.064 depending on climate zone and
in Table 402.1.1 a minimum R-10 (in units of h·ft²·°F/Btu)
perimeter insulation but if it’s heated an additional R-5 is
required with the height/depth subject to climate zone. For
commercial buildings, edge insulation of R 7.5 to R-20 is
required for all heated slabs again depending on climate
zone. In Canada the current CSA - B214 References CSA B214 –
07, requires no manufactured insulation, allowing for
equivalent R-5 based on resistance between underside of slab
and top of water table but this is overridden (and rightly
so) by at least two
regional codes. Furthermore the proposed National
Energy Code for Buildings (NECB) is calling for complete
under slab insulation for all heated slabs - of a value
dependant on climate zone. But as far as we can tell it
doesn't apply to buildings heated with overhead infrared. No
interior insulation is required for unheated slabs except in
the coldest climate.
If you read this carefully the
first thing that should get your attention is the
inconsistency in requirements and inconsistency in
insulation description…F-factors, U values or R
values….maybe it's time we all got on the same page...
So what is our position at
www.healthheating.com?
Well first off - to get a “D”
– you have to comply with code. In the absence of an
enforced energy code (i.e. it’s up to you to chose an “F”,
“D” or better) we’re saying use a minimum R-10 type 3 or 4
rigid. We’re also saying in the absence of enforcement and
in the presence of ‘value engineering’, anything with a
footprint exceeding 5000 ft2 should have a robust
slab heat loss analysis to see if it makes sense to reduce
insulation.
Why 5000 ft2?
Because 2500 ft2 is not out of the ordinary and
10,000 ft2 is commercial space by our definition.
When you hit the 5000ft2 and you’re thinking you
want to swap the one time capital cost (i.e. insulation
dollars) for long term operational energy dollars then you
need to do a robust analysis. You may not agree - but this is
our website and our opinion and we’re sticking to it unless
convinced otherwise.
For commercial buildings again we’re saying follow the codes
to get a “D” but to get an “A” or an “A+” do a full system
analysis based on the combined features of the architectural
systems and mechanical systems. There is a case to be made
for reduced insulation values in the interior spaces
depending on the project conditions.
What do we mean by this?
Well if you’re building a square 100,000 ft2
shopping center on top of a well drained rise formed
primarily with dry sandy soil and less than 10% chance of
flood waters ever approaching 15 ft. to 20 ft. under the slab there is
little performance benefit to insulating under the entire
slab interior. However, move that same structure next to a
well known flood plain, turn that square into a long narrow
rectangular building and you’ll have completely different
project to evaluate.
Our final thoughts - you get one chance to
insulate under a slab - do a thorough analysis to ensure the
best decision is made before the concrete is placed - and
remember once everything is installed the only wild card
left is the cost of energy. If you have the potential for
robust downward heat losses but are protected by insulation and
energy costs go up (and they will) then you're laughing...if energy costs go down then you will be paying less for
less energy. If you have no insulation and have robust
downward losses and energy costs go
up then - in very technical engineering talk - you're screwed. |
|
Bibliography
and endnotes:
-
"As above-grade components
of the building thermal fabric become more energy
efficient, the heat transfer between the building and
the ground becomes relatively more important."
citation: J. Neymark, J., Judkoff, R., Beausoleil-Morrison,
I., Ben-Nakhi, A., Crowley, M., Deru, M., Henninger, R.,
Ribberink, H., Thornton, J., Wijsman, A., Witte, M., IEA
BESTEST In-Depth Diagnostic Cases for Ground Coupled
Heat Transfer Related To Slab-On-Grade Construction,
Eleventh International IBPSA Conference, Glasgow,
Scotland, July 27-30, 2009
-
"floor heat loss can range
from 15% to 45% of the annual heating load." ibid
-
the Canadian housing stock
accounts for 17% of national end-use energy consumption,
primarily due to space heating. citation: Swan,
L., Ismet Ugursal, V., Beasuoleil-Morrison, I.,
Implementation of A Canadian Residential Energy End-Use
Model for Assessing New Technology Impacts, Eleventh
International IBPSA Conference, Glasgow, Scotland, July
27-30, 2009
-
Beausoleil-Morrison, I.,
Paige Kemery, B., Analysis of Basement Insulation
Alternatives, Mechanical & Aerospace Engineering,
Carleton University, April 30, 2009
Suggested reading:
-
ISO 13370:2007
Thermal performance of buildings -- Heat transfer via
the ground -- Calculation methods
-
Kehrer, M., Pallin, S.
Hygrothermal Material Properties for Soils in Building
Science, Journal of the National Institute of
Building Sciences. October, 2013.
-
Bean, R.,
All Points Bulletin, HPAC Magazine, November 2011.
Related links:
-
Below grade comparison
-
Downward heat loss
tools
-
Reflective bubble foil insulation
-
Walls for Cold Climates
|
|