Online educational resource on achieving indoor environmental quality with radiant based HVAC systems
Not for profit educational resource on indoor environmental quality.
 Bookmark and Share
Fundamentals of indoor environmental quality / thermal comfort and air quality solutions using radiant based HVAC

"Have you ever considered that most naysayer of the hybrid radiant based HVAC systems say the problem is you need two systems, one for comfort and one for ventilation; and yet many competent ventilation experts agree that independent ventilation systems are preferred – go figure."

Introduction

When it comes to radiant there are no shortages of myths, we address at least 45 of them at the website[i]; one undisputable whole truth about radiant is its role as an “enabler”.  Specifically when we talk about the hybrid radiant cooling system - it enables the preferred separation of thermal comfort from ventilation.[ii] Translation: it facilitates the use of 100% dedicated, ducted and distributed outdoor air. This system has many advantages in that its sole existence is for the exclusive tasks of dehumidification, deodorization and decontamination, i.e. there is no conflict in purpose. In comparison to all air systems, the air part of a hybrid is designed and assembled around significantly reduced air flows leading to smaller sized air handlers, filters, ducts, dampers and fabrication and installation accessories; all of the above translates to a more effective system for less capital cost and lower operating and maintenance costs. Additionally these dedicated duty systems are very effective at controlling the environmental conditions necessary for controlling microbial, hydrolysis, swelling in hygroscopic materials and in promoting respiratory and thermal comfort.

From an energy and exergy efficiency perspective, the sensible part of the hybrid radiant cooling systems is associated with tepid fluid temperatures in the range of 55°F to 70°F (13°C to 21°C) with high performance buildings using masonry type flooring; making them ideal for direct ground coupled exchangers, evaporative cooling with or without night sky radiation and promote the possibility of compressorless cooling systems; or at the very least the ability to bypass the compressor for all but peak loads. The high return temperature range of 60°F to 75°F (16°C to 24°C) also enables maximizes efficiency from cooling plants and reduces transmission gains.

Radiant system in general also serve the needs of the architect and interior designer with greater freedoms with space, the ability to comfortably use low VOC materials, as well as superior capacity in handling direct solar load with a quieter and more pleasant solution.

Design Considerations

As much as industry might want there to be a, “Radiant Cooling for Dummies”  - there isn’t – in fact I’d be disturbed to think that such a book would be published and end up…well…in the hands of a dummy. That’s a nice way of saying we have enough stupid radiant heating tricks out there we don’t need to pile on with radiant cooling fiascos. This is one type of system that requires the designer and contractors to understand the interactions and connections between buildings, the indoor environment and various HVAC systems and controls. It’s not difficult but it does require skills sets beyond the typical hydronics only or air only technician. It…well…yes… requires a hybrid radiant based HVAC designer and contractor.

So here is an abridged version of how it’s done.

First understand the objective in the hybrid design is to introduce dedicated lean ventilation air to the space reflecting the anticipated latent loads from occupants, infiltration and other sources. You will be using the dry supply air to maintain space operating conditions below the dew point of the radiant panel; and have panel surface and radiant asymmetry temperature limits within the range established by ANSI/ASHRAE 55 - Thermal Environmental Conditions for Human Occupancy.

Let’s look at a simplified example of a small 30' x 30’ x 10' classroom with a maximum occupancy of 30 people and a space sensible cooling load (qs ) calculated to be 28,584 Btu/hr (8.4kW) and space conditions maintained at 74°F (23.3°C) operative temperature (top ) and 50% rh. From the psychrometric chart, this gives a dew point temperature of ≈ 54°F (12.2°C) and a moisture content of ≈ 0.00896 lbH2O/lbdry .

1) Using a 100% outdoor air supply per person of 20 cfm[iii], the ventilation flow rate (Qv) becomes (all calcs in IP units):

Qv = 30 persons · 20 cfm per person = 600 cfm                                                                    [1]

2) The latent load (qL) due to occupants is calculated, using an estimate of 200 to 220 Btu/hr/per person (approximation from ASHRAE activity tables[iv]) as;

qL = 30 occupants x 220 Btu/hr/pp = 6,600 Btu/hr                                                                [2]

3) The humidity ratio differential () due to ventilation is calculated for the occupant latent load as;

qL = latent heat of vaporization (Lv ) · air flow rate (Q) · D in humidity ratio (Dω)                       [3]

qL = (60 min/h  · 1076 Btu/lb water · 0.075 lb air/ft3 ) · 600 cfm · 

qL = 4840 Btu-min/ft3-hr · 600 cfm · ()              

4) From formula [2] the occupant latent load, q= 6,600 Btu/hr, and now can be calculated using equation [3];

6,600 Btu/hr = 4840 Btu-min/ft3-hr · 600 cfm · (),

Rewritten to solve for ;                          

= qL / Lv · Q                                                                                                                       [4]

= 6,600 Btu/hr / (4,840 · 600 cfm)

≈ 0.00227 lbH2O/lbdry

0.00227 lbH2O/lbdry  represents the humidity ratio differential for 30 people.

5) For determining dew point, calculate the maximum anticipated humidity ratio (ωoccupied ) starting with a space operating condition of 74°F (23.3°C) @ 50%rh adding a 30 person load (infiltration and other possible latent loads ignored for this example):

ωoccupied = ωoperating + ωpeople …+ ωother                                                                                                     [5]

ωoccupied = ω(74°F@50%rh) + ω(30 people @ 220 Btu/pp)

ωoccupied
= 0.00896 lbH2O/lbdry + 0.00227 lbH2O/lbdry

ωoccupied = 0.01123 lbH2O/lbdry

From the psychrometric chart (Figure 1),

ωoccupied = 74°F @ 62.5%rh equals a dew point of 60.4°F

Radiant Cooling Calculation Psychrometrics

Figure 1. Lean supply air at 55°F @ 50% rh delivered to space to control moisture conditions below dew point of radiant panels. Shown is minimum floor surface temperature of 66°F based on ANSI/ASHRAE 55.

6) Establish the minimum allowable surface temperature of the radiant panel (tp); based on good practice, select for ≈ 2°F to 3°F (1°C to 1.5°C ) minimum Dt above the dew point :

tp = ωoccupied-dp + 3°F                                                                                                          [6]

t
p = 60.4°F + 3°F = 63.4°F (17.5°C)

Notwithstanding radiant asymmetry and comfort, 63.4°F (17.5°C) represents the lowest allowed panel surface temperature with a sufficient safety margin to prevent surface condensation.

7) Calculate sensible supply air capacity (qs): with an operating space dry bulb of 74°F (23°C) and designer choice supply dry bulb of 55°F[v], the sensible air capacity becomes:

qs = 60 min/h · (specific heat, Cp) · (density, ρ) · (air flow rate, Q) · Dt      [7]

qs = (60 min/h · 0.244 Btu/lb°F · 0.075 lb/ft3 ) · cfm ·  Dt

qs = 1.08 · cfm  · Dt

qs = 1.08 · 600  · (74°F - 55°F)

qs = 12,517 Btu/hr

12,517 Btu/hr represent the sensible air cooling capacity of the supply air; this value deducted from the 28,584 Btu/hr total sensible required, is what the radiant cooling panel must absorb.[vi]

8) The sensible cooling load placed on the radiant panel becomes:

qs,  panels  = Total load (sensible) – air cooled (sensible)                                      [8]

qs , panels  = 28,584 Btu/hr - 12,517 Btu/hr

qs , panels  = 16,069 Btu/hr

This 16,069 Btu/hr can be assigned to a radiant ceiling, wall or floor or combination of cooling panels if necessary.[vii]

9) The required radiant panel surface flux (heat absorption) becomes:

 qflux = qs, panel / Aavailable panel area                                                                                    [9]

 qflux = 16,069 Btu/hr / (30 ft x 30 ft)

 qflux = 17.85 Btu/hr/ft2

This 17.85 Btu/hr/ft2 can be absorbed from any type of radiant panel.

10a) For radiant ceiling cooling, the surface temperature (ts ) becomes:

 ts = top – (qflux / heat transfer coefficient[viii])                                                          [10a]

 ts = 74°F – (17.85 Btu/hr/ft2  / 1.94 Btu/hr ft2 °F)

 ts = 64.8°F > 63.4°F (safety margin temperature) > 60.4°F (occupied dew point) = good

Since 64.8°F (18.2°C)  is above the safety margin limit of 63.4°F (17.4°C) and more than the 60.4°F (15.8°C) occupied dew point this would be an acceptable solution.        

10b) For radiant floor cooling, the surface temperature (ts ) becomes:

ts = top – (qflux / heat transfer coefficientv)                                                             [10b]

ts = 74°F – (17.85 Btu/hr/ft2  /  1.23 Btu/hr ft2 °F)

ts = 59.5°F (15.3°C)

ts = 59.5°F < 60.4°F (occupied dew point) < 63.4°F (safe) & < 66°F min.

Since 59.5°F (17.5°C) is below the occupied dew point of 60.4°F (15.8°C) and below the acceptable 66°F (19°C) surface temperature for thermal comfort, this would be an unacceptable solution without modifications to rework design for; higher operative temperature (top) or increase panel surface area (A), add peak cooling panels or second stage cooling coils or improve zone enclosure to get sensible loads down.

10c) For radiant wall cooling, the surface temperature (ts ) becomes:

 ts = top – (qflux / heat transfer coefficientv)                                                                            [10c]

 ts = 74°F – (17.85 Btu/hr/ft2  / 1.41 Btu/hr ft2 °F)

 ts = 61.3°F

 ts = 61.3°F > 60.4°F (occupied dew point) < 63.4°F (safety margin temperature)

Since 61.3°F (16.3°C) is above the occupied dew point of 60.4°F (15.8°C) but below the acceptable safety margin surface temperature of 63.4°F (17.4°C) this is a riskier application and would be an unacceptable solution without modifications to rework the design for; higher operative temperature (top) or increase panel surface area (A), add peak cooling panels or second stage cooling coils or improve zone enclosure to get sensible loads down.

Now that we have determined the sensible load on the panel system and sensible and latent load on the air system, we need to determine the capacity of the cooling coil in the air handler.

11) Calculate sensible (qs), latent (ql) and total load (qt) for cooling and dehumidification load for the dedicated outdoor air system to take 600 cfm of 100% outdoor air from an example of 85°F @ 80%rh (h1, ω1) to a supply air of 55°F @ 50%rh (h2, ω2);

State point conditions from the psycrometric chart:

h1 = 43.44 Btu/lbdry

ω1 = 0.0210 lbH2O/lbdry

h2 =  18.17 Btu/lbdry

ω2= 0.0046 lbH2O/lbdry

h3 =  25.45 Btu/lbdry

ρ  = 0.0750 lb/ft3

Where,

hn = enthapy at state point

ωn = humidity ratio at state point             

ρ    = air density

12) Sensible (qs), latent (ql) and total load (qt) on coil is calculated using;

q   = 60 min/h · density (ρ)· air flow rate (Q) · enthalpy differential (Dh) [12]                       

q  = (60 min/h · 0.075 lb/ft3 ) · cfm ·  Dh

q = 4.5 · cfm  · Dh

qs= 4.5 · 600  · (h3 h2) = 2700 · (25.45 – 18.17) = 19,656 Btu/hr

ql = 4.5 · 600  · (h1 h3) = 2700 · (43.44 – 25.45) = 48,573 Btu/hr

qt = 4.5 · 600  · (h1 h2) = 2700 · (43.44 – 18.17) = 68,229 Btu/hr

 

Latent loads Radiant Cooling Calculation Psychrometrics

Figure 2. Primary load on the DOAS coil for cooling and dehumidification. Note: this is a simplified overview and does not represent all possible loads including heat recovery.

DOAS for Radiant Cooling

Figure 3. Overview of the operating characteristics for the hybrid radiant based HVAC system in the cooling mode.

In a nut shell, that is the why and how process for doing a radiant cooling system; albeit a simplified description since it does not describe re-heat nor heat recovery potentials of the system but a competent HVAC engineer or technician would be able to describe all the necessary processes for each application and choice in DOAS equipment.

It’s sufficient to say that radiant cooling is becoming a big thing especially for commercial buildings.  There is no need to pay attention to the myths nor is there any need to experiment. The applications and calculation procedures are proven and the working projects all over the world are demonstrating the energy and comfort features and benefits enabled by radiant based HVAC systems.[ix],[x]


[i] Radiant Mythology: myths about low temperature radiant heating and high temperature radiant cooling http://www.healthyheating.com/Radiant_Mythology/Radiant_Floor_Heating_Myths_.htm#.UrHdYeLDseI

[ii] Sensible loads: ASHRAE 55, ISO 7730, CSA F280 and Ventilation loads: ASHRAE 62.1, 62.2 and CSA 326

[iii] The actual cfm/person is determined by a method acceptable to the authority having jurisdiction, sample procedures are defined in ANSI/ASHRAE Standard 62.1 , 62.2 and CAN/CSA-F326-M91 (R2010)

[iv] 2009 ASHRAE Fundamentals Handbook, Chpt.18, Section 4

[v] This is purely based on experience but you can see how changing the target number will have a “flow through” effect on the design.

[vi] The 28,584 Btu/hr total load came from the heat gain calculation (not described in this example).

[vii] Bean, R. Together Forever (Using the ASHRAE Radiant Design Nomograph), HPAC Canada, March 2012.

[viii] *Heat transfer coefficients (htc) - are empirical values determined from experiments (ref.: ASHRAE, REHVA and ISSO)

[ix] Radiant Cooling Design Manual, Embedded Systems for Commercial Applications, Uponor, 2013

[x] Hydronic Cooling, idronics Journal of Design Innovation for Hydronic Professionals, Caleffi, July 2013


Additional resources:

  1. How to use the ASHRAE Design Graph for Radiant Panels
  2. Radiant Cooling 
  3. ASHRAE San Antonio Seminars
  4. ACCA Radiant and Hydronics Council - Roundtable
  5. Comfortech Radiant Cooling/Radiant Panel Alliance - Seminar
  6. Très Bien for large scale radiant cooling

Great article, it's nice when the laws of physics are plain to see, and we don't get the usual "opinion" driven design - Oohh- radiant cooling- it will rain and condense inside the room!" Geoff McDonell P.Eng.

 

Home | Seminars | Solutions | Heating Cafe | Contribute | Online Help | Bean's Blog | About Us | Glossary
Privacy Policy | Legal | Contact Us | Site Map |
Carlson-Holohan Award| Send Us Your Comments

Copyright © 2014 Healthy Heating. All rights reserved.1 2 3
Site developed by WebworX.ca
 
Donate using PayPal, Credit Cards Accepted